TA692FC-L-5 LoRaWAN API
Tip
This section applies to
TA692FC-L-5
.
Overview
Payload format in LoRA packet used by TA692FC-L-5
Uplink | port 10
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
data.RoomTemperature (High Byte) |
Room Temperature(°C) = D_Room_Temperature/10 |
0 ~ 400 |
1 |
data.RoomTemperature (Low Byte) |
||
2 |
data.SetTemperature (High Byte) |
Set Temperature(°C) = D_Set_Temperature/10 |
50 ~ 350 |
3 |
data.SetTemperature (Low Byte) |
||
4 |
data.CoolProportionalOutput |
Cool Proportional Output : 0-100% |
0 ~ 100 |
5 |
data.FanMode |
0:OFF 1:LOW 2:MED 3:HIGH 4: AUTO |
0 ~ 4 |
6 |
data.FanState |
0:OFF 1:LOW 2:MED 3:HIGH |
0 ~ 3 |
7 |
data.threshold (*) |
Temperature change: 0.2°C ~ 5.0°C |
2 ~ 50 |
8 |
data.SystemMode |
0:OFF 1:COOL 2:FAN-ONLY |
0 ~ 2 |
9 |
Data.CoolPBand |
P-Band for Cool : 1.0°C ~ 4.0°C |
10 ~ 40 |
10 |
Data.CoolItime (High Byte) |
I-Time for Cool : 5 ~ 180 |
5 ~ 180 |
11 |
Data.CoolItime (Low Byte) |
||
12 |
Data.Kfactor |
K-Factor : 1 ~ 9 |
1 ~ 9 |
Downlink | port 90
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
data.SetTemperature (High Byte) |
Set Temperature(°C) = D_Set_Temperature/10 |
50 ~ 350 |
1 |
data.SetTemperature (Low Byte) |
||
2 |
data.FanMode |
0:OFF 1:LOW 2:MED 3:HIGH 4:AUTO |
0 ~ 4 |
3 |
data.threshold [1] |
Temperature change: 0.2°C ~ 5.0°C |
2 ~ 50 |
4 |
data.SystemMode |
0:OFF 1:COOL 2:FAN-ONLY |
0 ~ 2 |
5 |
Data.CoolPBand |
P-Band for Cool : 1.0°C ~ 4.0°C |
10 ~ 40 |
6 |
Data.CoolItime (High Byte) |
I-Time for Cool : 5 ~ 180 |
5 ~ 180 |
7 |
Data.CoolItime (Low Byte) |
||
8 |
Data.Kfactor |
K-Factor : 1 ~ 9 |
1 ~ 9 |
Footnotes
Downlink | port 91
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
data.SetTemperature (High Byte) |
Set Temperature(°C) = D_Set_Temperature/10 |
50 ~ 350 |
1 |
data.SetTemperature (Low Byte) |
Downlink | port 92
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
data.FanMode |
0:OFF 1:LOW 2:MED 3:HIGH 4:AUTO |
0 ~ 4 |
Downlink | port 93
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
data.threshold [2] |
Temperature change: 0.2°C ~ 5.0°C |
2 ~ 50 |
Footnotes
D_update_threshold determines the minimum change in ambient room temp required to trigger a send event i.e. uplink. The range is from 0.2 to 5 centigrade. However, this parameter is limited by another named, “sending interval”, hardcoded 15 seconds.
e.g. if change in temp > 0.2°C, or, fan status change, or user press a button etc., sends uplink immediately
Downlink | port 94
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
data.SystemMode |
0:OFF 1:COOL 2:FAN-ONLY |
0 ~ 2 |
Downlink | port 95
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
Data.CoolPBand |
P-Band for Cool : 1.0°C ~ 4.0°C |
10 ~ 40 |
Downlink | port 97
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
Data.CoolItime (High Byte) |
I-Time for Cool : 5 ~ 180 |
5 ~ 180 |
1 |
Data.CoolItime (Low Byte) |
Downlink | port 95
Byte |
Data |
Content |
Range |
---|---|---|---|
0 |
Data.Kfactor |
K-Factor : 1 ~ 9 |
1 ~ 9 |